[NMR Pipe Protector Verification Results] Hospital #H
"NMR Pipe Protector" for preventing red rust in piping.
Preventing red rust leaching in the hospital's air conditioning chilled and hot water piping and demonstrating rust prevention effectiveness!
At Hospital #H, which was built 48 years ago, the air conditioning chilled and warm water piping using galvanized steel pipes (SGP) has shown significant deterioration due to red rust, leading to leaks. Therefore, we installed the red rust prevention piping extension device "NMR Pipe Protector." Before installation, we sampled the circulating chilled and warm water, and it was found that the total iron content in the water was 2.5 mg/l, indicating that red rust corrosion was progressing within the piping. Four weeks after the installation of our product, the total iron content in the chilled and warm water had significantly decreased to 0.4 mg/l. A sampling conducted six years after installation showed that the total iron content in the water further decreased to 0.2 mg/l, completely halting the progression of new red rust in the air conditioning chilled water piping. The existing red rust had transformed into insoluble, passivated black rust, with a volume reduced to one-tenth. [Introduction Overview] ■ Hospital Location: Hamamatsu City, Shizuoka Prefecture ■ Hospital Overview: 41 years old, 2 basement floors and 9 above-ground floors with 606 beds ■ Installation Date: December 2013 *For more details, please refer to the PDF document or feel free to contact us.
Inquire About This Product
basic information
[Installed Piping/Number of Installations] ■ Air conditioning chilled and hot water secondary (supply) header secondary side chilled and hot water supply pipe (SGP pipe 250mm)/PT-250DS×1 unit ■ Air conditioning hot water secondary (supply) header secondary side hot water supply pipe (SGP pipe 250mm)/PT-100DS×2 units ■ Others, 1st and 2nd building pumping and water supply system PT-150DS to 75DS×6 units *For more details, please refer to the PDF document or feel free to contact us.
Price range
Delivery Time
Applications/Examples of results
For more details, please refer to the PDF document or feel free to contact us.
catalog(10)
Download All Catalogs
Company information
~Extending the lifespan of old piping~ "NMR Pipe Protector" Cumulative installation record surpassing 4,300 buildings! (As of March 2022) Among them, over 3,000 installations in condominiums. = Domestic Achievements = New Chitose Airport Domestic Terminal, JR Sapporo Station (JR Tower Building), Imperial Theatre Building (Tokyo Marunouchi), Yaesu Exit Hall, Famous Bookstore Building (Shinjuku), Hotel Toyokaku (Kyoto), Hotel Serve Shibuya, Care House Shirasagi (Saitama), Kawanishi Private Kushi Elementary School, Food Processing Factory, Major Automobile Manufacturer Factory (Fukuoka Prefecture), Kumamoto Red Cross Hospital, etc. = International Achievements = Buckingham Palace, London City Hall, British Museum, BBC, Christ's College, University of Cambridge, Royal Bank of Scotland, Harrods Department Store, Royal Garden Hotel London, UK Parliament, etc. ★ Featured in the Media "NMR Pipe Protector" ★ Selected as one of the top 10 rust prevention technologies in the world in 2020 and introduced in a U.S. magazine! Case studies and customer testimonials have been featured in many media outlets, including TV Tokyo's "World Business Satellite (WBS)," TOKYO MX's "Corporate Spirit," and specialized newspapers "Condominium Management News" and "Air Conditioning Times."