Simultaneous measurement and display of the four air conditioning elements, with airflow calculation and heat quantity calculation functions.
The Anemo Hygrometer VC-1050 can measure not only the four air conditioning elements of wind speed, static pressure, temperature, and humidity, but also calculate airflow, heat quantity (calories), and maximum, minimum, and average differential pressure. It features a built-in data logger that allows measurement data to be downloaded to a PC (software required). Optional features include printer output and PC transfer, making it easy and quick to measure indoor ventilation, intake, and exhaust volumes in apartments and buildings with the measurement hood. (Compliant with JIS T8202) The measurement range includes wind speed from 0.05 to 4.99 m/s and 5.0 to 50.0 m/s (automatic switching between two ranges), static pressure and differential pressure from -1.999 to +1.999 kPa, temperature from -9.9 to +80.0°C, and humidity from 3.0 to 97.0%. It has an LCD graphic display (with backlight) that shows multiple parameters simultaneously, and it can be powered by a rechargeable Nicd battery or an AC adapter for both AC and DC use. The main unit dimensions are 220 (w) x 120 (h) x 110 (d) mm, and it weighs 2 kg. The probe dimensions are: wind speed and temperature 1: Ф8×150 mm with a 1.5 m cable, humidity and temperature 2: Ф12×140 mm with a 1.5 m cable. For more details, please contact us or refer to the catalog.