Inspection, adjustment, and balancing of air conditioning equipment and systems, as well as airflow measurement for complex air outlet shapes such as grills and diffusers.
● Lightweight and easy to handle, allowing for simple airflow measurement tasks to be performed by one person. ● Wide airflow measurement range: 85 to 4,250 m3/h ● Easy-to-read and user-friendly simple design with a full-color LCD No complicated calculations needed. Airflow is displayed immediately after pressing the start button. (Temperature and humidity are displayed simultaneously) ● Capable of determining the flow direction at intake and exhaust points ● Data logging function for up to 3,000 readings ● Measurement data can be saved with individual ID management ● Built-in back pressure compensation function to ensure accuracy at high airflow rates ● Equipped with atmospheric pressure compensation function ● Transparent hood for easy alignment with air conditioning vents The standard hood is made of transparent material, making it easy to align with air conditioning vents. The hood is foldable and does not take up storage space. ● Five types of optional hoods to choose from based on application A standard hood measuring 610×610mm is included. Additionally, five other hoods of different sizes are available (sold separately). ● Stand compatible with high ceilings (optional) A stand that can be extended from 1.2 to 2.5m is available (sold separately).
Inquire About This Product
basic information
Measurement Range Airflow: 40–4250 m³/h Temperature: 0–50℃ Humidity: 0–100% RH Measurement Accuracy Airflow: ±(3% of indicated value ±10) m³/h Temperature: ±0.5℃ Humidity: ±3% RH Display Resolution Airflow: 1 m³/h Temperature: 0.1℃ Humidity: 0.1% RH Communication Function Digital: USB Data Recording Function Up to 3,000 data points (internal memory) Power Supply 4 AA batteries Continuous Operating Time Approximately 9 hours
Price information
-
Delivery Time
※Please check each time.
Applications/Examples of results
● For inspection and adjustment of air conditioning equipment Even in buildings with many measurement points, simply covering the air conditioning vents with a hood allows for effortless air volume measurement. ● For verifying the effectiveness of air conditioning cleaning By comparing the air volume before and after cleaning, the cleaning effect can be visualized in numerical terms. ● Air volume check after air conditioner cleaning The cleaning effect (change in air volume from the air conditioner) can be confirmed after cleaning the air conditioner.
catalog(1)
Download All CatalogsCompany information
Introducing measuring instruments, packaging materials, and logistics equipment. We always deliver a new lineup of products! We provide information on special deals, such as manufacturer collaboration products, as well as limited-time and limited-quantity items.