Red Water Countermeasures (Hotel Hot Water Supply) [Magnetic Water Treatment Device Vol. 9]
Installed with a partial bypass method on return pipe 65A! Introduction of a case where red rust in the boiler turned into black rust and red water stopped.
There was a complaint that red water was coming out of the hot water faucet in the guest rooms within three years of the hotel's completion, and various measures were taken, but the issue was not resolved at all. As a result, a Polar magnetic water treatment device "Model PI-25F" (3-point set) was installed in a partial bypass configuration on the return pipe 65A, treating about 20% of the circulating water volume. As a result, it was confirmed that the red rust in the boiler had turned into black rust, and the red water had stopped. [Case Study] ■ Issues - Despite the piping being made of stainless steel and plastic, red water occurred. - The cause of the red water was corrosion due to an abnormal oxidation reaction of dissolved oxygen (DO) in the water inside the steel hot water heater. ■ Measures - A Polar magnetic water treatment device "Model PI-25F" (3-point set) was installed in a partial bypass configuration on the return pipe 65A. *For more details, please refer to the PDF document or feel free to contact us.