Grounding transformer for measuring instruments (current transformer CT, potential transformer PT) 'KBG-□□□'
KBG-□□□
Indoor PT products that can convert voltage! Please use them first. Instruments for distribution boards, control panels, distribution panels, and panels.
KBG-□□□ is our indoor 1.15 kV transformer (PT). The primary voltage is 380/√3V or 440/√3V. It is used for zero-sequence voltage detection (tertiary) during faults in ungrounded lines. This product is a single-phase transformer, and three units are combined for use, with the connection method being Y connection for primary and secondary, and broken delta connection for tertiary. When the bus voltage is applied to the primary side, the secondary side is used for relaying and measurement, while the tertiary side can be used for zero-sequence voltage detection. On the tertiary side, zero-sequence voltage meters, OVGR (overvoltage ground relay), ground fault confirmation lamps, CLR, SGR, DGR, etc., can be connected for use. For inquiries, please contact "lightstar_1979@yahoo.co.jp".
Inquire About This Product
basic information
【Specifications】 - Primary Voltage (Pri.Volt.): 220/√3V ~ 750/√3V - Secondary Voltage (Sec.Volt.): 110/√3V or 190/√3V - Tertiary Voltage (Ter.Volt.): 110/√3V or 190/√3V - Rated Load: Secondary 50VA, Tertiary 100VA - Class: KS C 1706 Class 1.0, IEC 60044-2 Class 1.0/3P, JEC 1201 1P/3G - Frequency: 60Hz (standard), 50Hz (upon request) - Secondary Overvoltage Multiple: 1.1Vn Continuous / 1.9Vn 30s - Material of Main Body: Iron case - Dimensions: 110×150×111 (Width×Height×Depth. Unit: mm) - Weight: 5000g
Price information
KBG-□□□: 10,950 yen
Price range
P1
Delivery Time
P3
※There is an agency in Yokohama, Japan, that has stock available.
Applications/Examples of results
It is a transformer for measuring instruments used for voltage reduction.
Detailed information
-
This is how to place an order for KBG-□□□. Please refer to it.
-
This is the specification for KBG-□□□. Please refer to it.
-
This is the outline diagram of KBG-□□□. Please refer to it.
-
This is the wiring diagram for KBG-□□□. Please refer to it.
Line up(8)
Model number | overview |
---|---|
KBG-111 | ・Primary voltage: 380/√3V ・Secondary voltage: 110/√3V ・Tertiary voltage: 190/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-112 | ・Primary voltage: 380/√3V ・Secondary voltage: 110/√3V ・Tertiary voltage: 110/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-121 | ・Primary voltage: 380/√3V ・Secondary voltage: 190/√3V ・Tertiary voltage: 190/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-122 | ・Primary voltage: 380/√3V ・Secondary voltage: 190/√3V ・Tertiary voltage: 110/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-211 | ・Primary voltage: 440/√3V ・Secondary voltage: 110/√3V ・Tertiary voltage: 190/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-212 | ・Primary voltage: 440/√3V ・Secondary voltage: 110/√3V ・Tertiary voltage: 110/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-221 | ・Primary voltage: 440/√3V ・Secondary voltage: 190/√3V ・Tertiary voltage: 190/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
KBG-222 | ・Primary voltage: 440/√3V ・Secondary voltage: 190/√3V ・Tertiary voltage: 110/√3V ・Load: Secondary 50VA, Tertiary 1000VA (1min) ・Class: KS C 1706 1.0, IEC 60044-2 1.0/3P ・Frequency: 60Hz (standard), 50Hz (upon request) ・Secondary overvoltage multiple: 1.1Vn Continuous / 1.9Vn 30s |
catalog(1)
Download All CatalogsCompany information
Our company was founded in 1979 and has grown into a manufacturer of products that can observe electrical data through early analog instruments, digital meters, wireless, and the internet. This development is driven by the strong will of our employees to walk alongside our customers. Additionally, we are committed to thorough customer-centric operations while actively investing in technological development at our affiliated research institute. We strive to meet our customers' diverse needs through more differentiated services. In our case, we have become well-known in South Korea for our measuring instruments (analog, digital meters, and CT, VT). We have been exporting to Japanese companies for over a decade, and we have registered with Ipros to introduce our products to more Japanese customers. In 2022, we registered as a corporation in Tokyo and have since relocated our corporate office to Osaka as "LIGHTSTAR JAPAN." We also have Japanese staff on-site, and we look forward to your support.